language
Email Us

Clamp Type Vortex Flowmeters (FVF80-J)

FvLuoky multifunctional vortex flow meter, can widely cope with liquid, gas, and steam measurement in the industry. The imported microprocessor design filters out error signals and vibration interference signals, and can optionally come with temperature and pressure compensation functions.

vortex flow meter sensor
  • vortex flow meter sensor
Share It :

Main Feature of Clamp Type Vortex Flowmeters (FVF80-J)

  • Display: Three-row LCD showing flow, cumulative amount, percentage, temperature, pressure, etc.

  • Accuracy: ±1%, ±0.5%

  • Four-piece piezoelectric ceramic technology to eliminate the impact of vibration

  • 4~20mA and pulse output, compatible with HART and RS485 communication

  • Probe and converter are universally interchangeable

  • Explosion-proof cast aluminum housing


Parameter of Clamp Type Vortex Flowmeters (FVF80-J)

Measurement MediumLiquid, Gas, SteamField Display3-row LCD display
Pipe Diameter15, 20, 25, 32, 40, 50, 65, 0, 100, 125, 150Current Output4~20 mA
200, 250, 300, 350, 400, 450, 500mmCurrent LoadRohm=(Vdc-12)*30
MaterialSUS304/SUS316L/2205Pulse OutputEngineering unit pulse
Accuracy+1-0.5% read value(Range ratio 1:5)Resistance Load1000Ω-5000Ω
+/-1.0% read value(Range ratio 1:10)Communication ProtocolHART (compatible) or RS485 (MODBUS Protocol)
UnitsNm³/h, Nm³/ m, Nm³/ s, m³/d, m³/ h, m³/mData StorageOperating parameters and total flow values are stored in EEPROM
m³/s, Vh, Vm, Vs, t/d, t/h, t/m, kg/d, kg/hAnd can be stored for more than ten years
kg/m, kg/s, g/h, g/m, g/sHousing MaterialCast aluminum
Repeatability+/-0.2% of readingPower Supply12~32 VDC
Connection TypeFlange type/Clamp type/Hoop typeLithium battery
Flange SpecificationJIS 10K/JIS20K/JIS 40KElectrical InterfaceM20*1.5, 1/2NPT
ANSI 150#/ANSI 300#/ANSI 600#Buttons3 built-in buttons for operation and display control
DIN PIN 10/PN 16/PN25/PN 40/PN 63Ambient Temperature-30~+60℃
Medium Temperature-40~+120℃Relative Humidity5-95%
-40~+250℃Other components
40~+420℃Pressure SensorUsed for pressure compensation
Pressure1.6MPa, 2.5MPa, 4.0MPa, 6.3MpaSignal Output24V DC+4~20mA (two-wire)
Explosion-Proof GradeExd IIC T4~T6Temperature SensorUsed for temperature compensation
Ex iallCT4~T6Signal OutputPT100
Protection GradeP65/67IntegratorIntegrated display of temperature, pressure, and flow
Structure TypeIntegrated type, Split typePower Supply/Signal220 VAC/24 VDC, 4~20 mA output


Clamp Type Vortex Flowmeters (FVF80-J) Application Field

  • Water Treatment

  • Oil and Gas

  • Chemical Industry

  • Food and Beverage

  • Power Generation

  • Pharmaceuticals


Dimensions Of Clamp Type Vortex Flowmeters (FVF80-J)

Dimensions Of Clamp Type Vortex Flowmeters (FVF80-J)


FVLUOKY Field Instruments Inquiry
Pictures or documents for technical requirements (optional)
Related Vortex Flowmeters for Reference
FVLUOKY News
FuYi Intelligent Instrument (Shanghai) Co.,Ltd.
3rd Floor, Building A, No. 205, Jianding Road, Fengjing Town, Jinshan District, Shanghai, China, 201502
+86-19280460621 Dora.chen@fvluoky.com
3rd Floor, Building A, No. 205, Jianding Road, Fengjing Town, Jinshan District, Shanghai, China, 201502
Dora.chen@fvluoky.com
+86-19280460621
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Visit our cookie policy to learn more.